(1) Referencing the Initial Setting Tool database
Selecting the connected indoor units from the database allows the cooling capacity, fan power consumption
and standby electric power to be set automatically.
Models that cannot be selected by type or name should be registered manually using the procedure in (2)
"Manual input" below.
Procedures
1. Click "Unit info.".
The indoor unit settings screen will be displayed.
2. In "Unit type", select [Air-conditioner], [Air-conditioner (A-control)], [Air To
Water], [LOSSNAY] or [LOSSNAY with heater/humidifier].
3. In "Model type", select the indoor unit type selected in "Unit type".
4. In "Model name", select the model name for the indoor unit.
5. In "Power supply frequency", select the frequency of the power supply.
6. Click [OK].
(2) Manual input
Check the indoor unit catalog (specifications) and then enter the "Cooling capacity" and "Fan power
consumption".
Procedures
1. In "Cooling capacity", enter the cooling capacity (kW) of the indoor unit.
2. In "Fan power consumption", enter the fan power consumption (kW) of the indoor unit.
3. In "Standby electric power", enter the standby electric power (kW) of the indoor unit.
g
(
y
yp )
Model
Power source
Cooling capacity
(Nominal)
Power input
Current input
Heating capacity
(Nominal )
Power input
Current input
External finish
External dimension H x W x D
Net weight
Note
• The cooling capacity cannot be entered for a LOSSNAY.
• Set the cooling capacity for an indoor unit between 0 and 999.999 [kW].
• Set the fan power consumption for an indoor unit between 0 and 999.999 [kW].
• Set the standby electric power for an indoor unit between 0 and 1.000 [kW].
• For "Standby electric power", the default setting of 0.005 [kW] is recommended.
• To exclude absent tenants from charge calculation, set the cooling capacity, fan power consumption and
standby electric power all to "0" (zero).
Note however that you must restore the original settings when a tenant is again in residence.
WT07442X02
PLFY-P20VLMD-E
PLFY-P25VLMD-E
1-phase 220-240V 50Hz, 1-phase 220-230V 60Hz
kW
2.2
kcal / h
1,900
BTU / h
7,500
kcal / h
2,000
kW
0.072 / 0.075
A
0.36 / 0.37
kW
2.5
kcal / h
2,200
BTU / h
8,500
kW
0.065 / 0.069
A
0.30 / 0.32
mm
290 x 776 x 634
in.
11-7/16 x 30-9/16 x 25
kg (lbs)
23 (51)
PLFY-P32VLMD-E
2.8
3.6
2,400
3,100
9,600
12,300
2,500
3,150
0.072 / 0.075
0.072 / 0.075
0.36 / 0.37
0.36 / 0.37
3.2
4.0
2,800
3,400
10,900
13,600
0.065 / 0.069
0.065 / 0.069
0.30 / 0.32
0.30 / 0.32
Unit : Galvanized
290 x 77
11-7/16 x 30
23 (51)
24 (53)
89
<Example>
For the "PLFY-P32VLMD-E" in the table at
left, the settings are as follows:
Cooling capacity: 3.6 kW
Fan power consumption: 0.072 kW (in 50 Hz
regions)
0.075 kW (in 60 Hz
regions)