Mitsubishi Electric AE-200A Instruction Book page 112

Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

CSV data (apportioned calculation results) "Energy management block"
* If "-2" is shown in "Status", data was not carried over for that day because apportionment could not be calculated for that day.
Unit-related item sheet
(1) Check that the trial run was carried out successfully.
① Enter the date and time for the billing function trial run period.
② Check that the trial run was able to be carried out successfully (with no errors) during the trial run and, if so,
put a check in the check column.
③ Cause an error and check that the error is displayed. If so, put a check in the check column.
(2) Complete the check sheet using the CSV data for the AE-200 energy management block for
1-day intervals.
④ In the check sheet, enter the amounts of operating electric energy and standby electric energy for unit
prices 1-5 for each of the outdoor units.
⑤ In the check sheet, enter the amounts of operating electric energy and standby electric energy for unit
prices 1-5 for each of the indoor units.
(3) Check that the total amount of electric energy is correct.
⑥ Check that electric energy totals for the indoor and outdoor units connected to each electricity meter and
the electricity meter differences are more or less identical.
• Because the 2nd decimal place in fractions in the total electric energy figures are rounded off so that there
is only one decimal place, the figures may not match perfectly.
• The actual electric energy calculations may not match perfectly due to differences in the times when visual
confirmation was carried out.
⑦ Check that electric energy was able to be apportioned correctly for each unit price and put a check in the
check column.
• Check that the amounts of operating electric energy and standby electric energy for the unit price set are
not "0".
If the amounts are "0", check that the settings are set correctly. For details, refer to section 8-6 (3) "If there
is a unit with "0" amount of operating electric energy" or 8-6 (4) "If there is a unit with "0" amount of standby
electric energy". If the settings are incorrect, carry out the billing function trial run check again.
Even if the amount is "0", the unit may not be running or the electric energy consumed may be small. If the
settings are correct, check the charge parameter.
• Check that total values for operating electric energy and standby electric energy are more or less the
same as the metering device electric energy for the same system.
Note
• Check that the amount of standby electric energy is apportioned by proportion of cooling capacity when
not in use.
• If [Not apportion] is set for the amount of standby electric energy, it will all be taken to be operating electric
energy and the amount of standby electric energy will be "0".
(4) Specified date calculation using the Charge Calculation Tool.
Check that the correct charge is output.
For information on the output method, refer to section 3-1 "Specified date calculation (LAN connection)" or
3-2 "Specified date calculation (USB)".
WT07442X02
112