7. To receive an e-mail alarm when the temperature or the humidity exceeds certain predetermined values, set
the ON- and OFF-thresholds for both the upper and lower limit temperatures.
To avoid frequent ON/OFF cycling, the minimum differential between the ON- and OFF-threshold values
should be 1ºC (2ºF).
8. Click [Save] after completing the settings.
[1] Offsetting the measured temperature/humidity values
To set the offset value for the measured values, click [Acquire] to acquire the current value, and set the offset
value according to your usage environment.
Note
• If AI controller connection settings for a given centralized controller have not been saved, the "measurement
value" will not be displayed even when [Acquire] is clicked.
• When registering an AI controller for the first time, the "measurement value" cannot be acquired. To input
the "offset value" after acquireing and checking the "measurement value", once the setting information
must be sent to the centralized controller. After registering the AI controller and temperature/humidity
sensors, send the settings data to the centralized controller. (See section 6-4-3 [5] "Send".)
• The default offset value for temperature sensor is "0.0". The settable offset value range is between -10.0ºC
(-18.0ºF) and +10.0ºC (+18.0ºF).
• The default offset value for humidity sensor is "0.0". The settable offset value range is between -10.0%
and +10.0%.