Low Limit Outside of
Circuit
Low limit Outside of
Table
Low Output Limit less
than Zero
Monthly Periods Must Be
Phased
No Room for Function
Block
Number of Frames Out of
Range
Out of EEPROM Memory
Out of RAM Memory
Output Limits Equal
Pairs Inconsistent
Request Made with
Invalid Tag
Requires a Deviation
Parameter
Requires Input
Parameter
Requires Setpoint
Parameter
RJ Not in Curve
Temperature Constant
Not Programmed or Less
Than Zero
Temperature Input Not
Programmed or Less
Than Zero
Temperature Reference
Not Programmed or Less
Than Zero
Table 9-4 Error Messages (continued)
Description
AI circuit low limit is < voltage limit of -500 mV.
For thermocouple or RTD, Range Low limit is < the
low limit for that type.
A current output (CAT) low limit is less than zero.
Periodic Timer CV period is monthly but no phase is
defined.
System has used all allocated function blocks.
Rolling Average CV # of Samples is less than 1 or
greater than 60.
No more static memory or EEPROM memory.
No more RAM available.
Output (range) limits (low and high) must be unequal.
Applies to custom AI or Function Generator CV.
Curve has Xn but no Yn or vice versa. Curve does
not have at least 2 X,Y pairs.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Deviation alarm does not contain deviation.
Alarm does not contain an input.
Alarm does not contain a setpoint.
AI is custom type, class thermocouple, RJ enabled
but curve does not contain 0-65 degrees C (32-149
degrees F).
F0 Sterilization CV Temperature constant is not
programmed or is less than zero.
F0 Sterilization CV Temperature Input is not
programmed or is less than zero.
F0 Sterilization CV Reference Temperature is not
programmed or is less than zero.
Video Recorder – User Manual
Diagnostic and error messages
User Action
Change circuit low limit to > -500
mV.
Change limit to within specified
limits for that type. (Table 4-3)
Change current output (CAT) low
limit to greater than or equal to
zero.
Change Periodic Timer phase.
Verify programming of affected
function block.
Change # of Samples to 1-60.
Verify programming of affected
function block.
Verify programming of affected
function block.
Change to unequal limits
Program a Y for each X or vice
versa. Program at least 2 X's and
2 Y's.
Verify programming of affected
function block.
Program alarm with deviation.
Program alarm with input.
Program alarm with a setpoint.
Y values must contain 0-65
degrees C (32-149 degrees F).
Program Temperature constant
with value greater than or equal to
zero.
Program Temperature input with
value greater than or equal to
zero.
Program Reference Temperature
with value greater than or equal to
zero.
257