Ramp segments
Time = amount profile will change toward next soak Value
when the Ramp Increment discrete switches on.
Value = not used with ramp segment.
Segment #3
Value
Segment #1
Value
Segment #1
Time
ATTENTION
External ramp type's TIME prompt is in engineering units of the PV, not in time units (seconds, minutes, or
hours).
To increment toward a lower soak value, enter a positive TIME amount. The Setpoint Profiler "knows" to
increment or decrement this amount toward the next soak value.
Ramp Type = External
Features of this ramp type
* First and last segments must be soaks
* No consecutive ramps or soaks
Segment #3
Time
Ramp Increment Off-to-On
Segment #2
Elapsed time

Figure 5-6 External Ramp Type

Video Recorder – User Manual
Segment #2 Time
Segment #2 Time
Segment #2 Time
causes increme ntal value
change toward next soak
Value
Setpoint Profiler
Soak segments
Time = duration of soak
Value = value of soak