Standard Splitter Output (STD SPLITTER)
This function can be used for heat/cool applications. It is a deadband-based splitter that divides a Split
loop's output (-100% to +100%) into two outputs CVn A1 and CVn A2, both of which are zero when the
loop output is zero (Figure 4-14). A deadband provides a range of loop output within which both split
outputs remain at zero. For overlapped outputs, use Advanced Splitter. Note: A third output CVnA3 is
displayed Online and should be ignored.
CV A2
Table 4-42 describes the Standard Splitter prompts. See Table 4-2 for additional prompts.
Prompt
RANGE LOW
OFF or number
RANGE HIGH
INPUT
OFF, analog parameter,
number
FEEDBACK #1
AOn BC, LPn BC, CVn BC
FEEDBACK #2
AOn BC, LPn BC, CVn BC
OUTPUT
OFF or number
DEADBAND
100
0
-100
PID Output %

Figure 4-14 Standard Split Output Function

Table 4-42 Standard Splitter Prompts

Range/Selections
Video Recorder – User Manual
Programming Function Blocks and Features
Deadband
0
Enter the output's display limits. Output is not clamped or
flashed when it exceeds these limits.
Input source. Typically, this is the output value (OV) of a
Split Output type of loop.
Enter an AO, LP or CV for the back calculation value (BC)
of the analog output assigned to the A1 output.
Enter an AO, LP or CV for the back calculation value (BC)
of the analog output assigned to the A2 output.
Deadband up to 10% of the input span. In this range, both
split outputs will remain at zero.
100
CV A1
0
+100
Definition
135