Toshiba GR200 Series Instruction Manual page 978

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Technical data
Analog Inputs
Rated current In
Rated voltage Vn
Rated Frequency
Overload Rating
Current inputs
Voltage inputs
Burden
Phase current inputs
Earth current inputs
Sensitive earth fault inputs
Voltage inputs
Power Supply
Rated auxiliary voltage
Superimposed AC ripple on DC supply
Power Supply Interruption Withstand Period
(IEC60255-11)
Power consumption
Either 1A or 5A (specified when the ordering)
100V to 120V
Either 50Hz or 60Hz (specified when the ordering)
4 times rated current continuous
5 times rated current for 3 minutes
6 times rated current for 2 minutes
30 times rated current for 10 seconds
100 times rated current for 1 second
250 times rated current for one power cycle (20 or 16.6ms)
2 times rated voltage continuous
2.5 times rated voltage for 1 second
 0.1VA at In = 1A,  0.2VA at In = 5A
 0.3VA at In = 1A,  0.4VA at In = 5A
 0.3VA at In = 1A,  0.4VA at In = 5A
 0.1VA at Vn
24/48/60Vdc
(Operative range: 19.2 – 72.0Vdc)
48/125Vdc
(Operative range: 38.4 – 150.0Vdc)
110/250Vdc
(Operative range: 88.0 – 300.0Vdc)
 15%
110/250Vdc rating : 50ms
 15W (quiescent)
 25W (maximum)
- 964 -
6F2S1931 (0.20)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)