Supervision of task operation (RUN error)
9.2.8
Task operations in the IED are monitored every two minutes. Error messages can be screened
when the tasks stop. The tasks are supervised every 15 minutes if they are idling.
Error level
(i)
The error level has been set at level 1 (Serious error) unconditionally.
Error message
(ii)
When detecting an error, the error message can be shown on the LCD and the LED is lit.
Table 9.2-16 Error messages provided by the supervisor in MNT_LOGIC
Message and level
CP1M(RUN) error
Error level
Table 9.2-17 Detailed information in Hexadecimal in MNT_LOGIC
Display
area
10000000: Supervision function itself
Top
20000000: Idle task (1)
row
40000000: Idle task (2)
WW XX YY ZZ
Middle
WW:
FB index in PCM (2)
XX:
FB index in PCM(1)
row
YY:
FB index in SSP3(2)
YY:
FB index in SSP3(1)
WW XX YY ZZ
Bottom
WW:
FB index in CONVSET
XX:
FB index in NMT
row
YY:
FB index in 200MS(2)
YY:
FB index in 200MS(1)
Meaning of the information
Detection of the stopped task in the IED
Serious error (Level 1)
Meaning of the detailed information
Left column
- 475 -
Right column
WW XX YY ZZ
WW:
FB index in SSP2(2)
XX:
FB index in SSP2(1)
YY:
FB index in SSP1(2)
YY:
FB index in SSP1(1)
WW XX YY ZZ
WW:
FB index in 100MS (2)
XX:
FB index in 100MS(1)
YY:
FB index in 10MS
YY:
FB index in 5MS
WW XX YY ZZ
WW:
FB index in SUB4
XX:
FB index in SUB3
YY:
FB index in SUB2
YY:
FB index in SUB1
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)