Toshiba GR200 Series Instruction Manual page 571

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Edit GOOSE subscribe
GOOSE subscribe function is configured to receive GOOSE messages published
by other IEDs. Figure 10.3-21 exemplifies the GOOSE Subscribe screen; the user
can select the necessary signals to be added. For example, "Bay1 GBU200" is the
current IED; "Bay2 GRZ200" is the other IED. "List 1" is GOOSE publisher of
GRZ200; "List 2" is GOOSE subscriber for GBU200. The user can select the
GOOSE publisher from GRZ200 and add to the GOOSE subscriber of GBU200.
In the example shown below, select the required variable and click Add. Similarly,
the user can delete the variables.
When the user adds a signal to the GOOSE subscribe list from the other IED,
then the same signal is automatically added in the Signal List of the current
IED.
List 1
Figure 10.3-21 GOOSE Subscribe
Note: The user can monitor about the GOOSE message on the LCD screen. See sec.
10.3.8.
Edit Control function
The Data IDs (i.e., Signal Number) starting with "5" is used for control function
when the IED has the control function by default. The user should check whether
the required signals are mapped in the default configuration. The user can edit
and add the control signals to the LN as described in section 10.3.3(iv).
In an IED, usually an output Data ID of a protection function is assigned to LN
variable. However, for the control application, the IED is capable of receiving
command from the SAS server. To control a device (such as a circuit breaker), the
input point* (Data ID) in the control application should be configured to receive
commands from the SAS sever (that is, selecting, operating or cancel command).
- 557 -
6F2S1931 (0.20)
List 2
List 2
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)