Toshiba GR200 Series Instruction Manual page 480

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Error outputs with contacts and binary output circuits
(iii)
Automatic supervision function drives a contact of the power supply module (PWS)† when an
error occurs without warning; additionally, binary output circuits (BOs‡) will be locked out to
drive when serious error (Level 1=Critical error) is detected.
Table 9.1-4 FAIL contact, BO, LED outputs depending on levels
Error
Levels
Screw No. 1
0: No error
1:Serious
2:Serious(Comm.)
3:Minor
4:Alarm
5:Warning
Error output by PWS contact†
If serious error (Level1) is detected by Automatic supervision function, normally-closed-contact
(N/C) on FAIL1 and FAIL2 terminals is closed. On the other hand, the N/O contact is open on
the serious error, as shown in Table 9.1-4.
Locking out of BO circuit operation‡
BO is locked out to operate, when serious error (Level1) occurs. Serious error stops trip signal
generations to the BO circuit. When serious error is removed, the operation will be recovered.
†Note: See Chapter
is in Form-C; terminal-screw No. 2 & 4 (8 &10) are provided with the common.
‡Note: BO is discussed in Chapter
Affection of application operation by error levels
(iv)
The error levels influence the operation of relays and general control functions.
Table 9.1-5 Operation states in the IED applications affected by the error levels
Levels
0: No error
1: Serious
2: Serious (Comm.)
3: Minor
4: Alarm
5: Warning
†Note: Serious (Comm.) can be related to communication of tele-protection applications.
PWS† contact outputs
FAIL1 terminal
Screw No. 3
(N/C)
(N/O)
Open
Closed
Closed
Open
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Technical description: Power supply module
Relay applications
Stopped
Not affected†
Not affected
Not affected
Not affected
- 466 -
FAIL2 terminal
Screw No. 7
Screw No. 9
(N/C)
(N/O)
Open
Closed
Closed
Open
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Technical description: Binary output circuit
Control applications
Stopped
Not affected
Stopped
Not affected
Not affected
6F2S1931 (0.20)
BO‡ locked out
Not locked out
Locked out
Not locked out
Not locked out
Not locked out
Not locked out
. FAIL1 (FAIL2) contact
.
Notes
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
Error
LED
Off
On
On
On
Off
Off