settings. Table 4.4-3 shows the respective settings and ranges in BI1A and BIO5A.
Table 4.4-3 Setting items for binary input circuits
Setting item
1
THRES_Lvl
Common
CMP_NUM
BI1_CPL
BI1
On Delay Timer
Off Delay Timer
INVERSE-SW
BI2_CPL
BI2
On Delay Timer
Off Delay Timer
INVERSE-SW
BI3_CPL
BI3
On Delay Timer
Off Delay Timer
INVERSE-SW
.....
.....
n
BI
_CPL
n
BI
On Delay Timer
2
Off Delay Timer
INVERSE-SW
Note: Setting items are provided in each slot; see Figure 4.4-3. Also, see section 4.4.6 (i).
1
n
Note: BI
_CPL and other settings are provided for all binary input circuits. That is, we
2
have 18 CPLs for BI1A; we have nine CPLs for BIO5A.
Note: Each item above is required to set at every IO_slot.
3
Range
Low/High
Threshold level for input voltage
4 to 9
Number of times in the filter
Off/On
Switch of programmable operation in BI1
0.000 to 300.000
s
Value in the on-delay timer
0.000 to 300.000
s
Value in the off-delay timer
Normal / Inverse
Inversion operation of BI1 signal
Off/On
Switch of programmable operation in BI2
0.000 to 300.000
s
Value in the on-delay timer
0.000 to 300.000
s
Value in the off-delay timer
Normal / Inverse
Inversion operation of BI2 signal
Off/On
Switch of programmable operation in BI3
0.000 to 300.000
s
Value in the on-delay timer
0.000 to 300.000
s
Value in the off-delay timer
Normal / Inverse
Inversion operation of BI3 signal
.....
Off/On
Switch of programmable operation in BI
0.000 to 300.000
s
Value in the on-delay timer
0.000 to 300.000
s
Value in the off-delay timer
Normal / Inverse
Inversion operation of BIn signal
- 277 -
6F2S1931 (0.20)
Contents
.....
n
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
Default
Low
4
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
.....
Off
0.000
0.000
Normal