Trigger settings for PLC programming
7.3.2
If the PLC program instructs the operation of the disturbance recorder, the user should set the
[Trigger ID1] to [Trigger ID4]. That is, the program-output points should be set for the settings
[Trigger ID1] to [Trigger ID4]; then, set On for the [Trigger SW1] to [Trigger SW4], respectively.
Screen information
7.3.3
Figure 7.3-2 indicates the maximum number of the recording operations as the number is
changed depending on the time settings, which are shown in Table 7.3-1. Figure 7.3-3 shows
the operation time and the date for the disturbance recorder and the figure illustrates five
disturbance phenomena have been memorized in the IED.
Disturbance Record
10:48
_Record List
Number of items
5/77
Clear Records
Figure 7.3-2 Running counter and Max number in the disturbance recorder
Screen scroll down
Figure 7.3-3 Detail information in the disturbance recorder
The information in the disturbance recorder is managed in the COMTRADE format,
hence, the user can transfer the disturbance recording file to the PC using the engineering tool
'GR-TIEMS'. Figure 7.3-4 shows the example of the GR-TIMES screen. For more information,
Chapter Engineering tool
see
1/2
>
+
Max. recording number for Disturbance phenomena
Operating counter
Disturbance Record
10:48
#1
2012-07-25
10:48:21.223
#2
2012-07-21
01:15:55.018
#3
2012/07/21
13:11:29.621
#4
2012-07-02
23:32:09.015
#5
2012-06-20
09:37:48.915
.
- 378 -
1/5
a
Disturbance record#1
b
Disturbance record#2
c Disturbance record#3
d
Disturbance record#4
e
Disturbance record#5
6F2S1931 (0.20)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)