Toshiba GR200 Series Instruction Manual page 154

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting items
TOC*R
OC*-RTMS-IEEE
OC*-RTMS-US
OC*-RTMS-ORG
OC*-k
OC*-a
OC*-c
OC*-kr
OC*-b
Mode / range
0.00 - 300.00
0.010 - 50.000
0.010 - 50.000
0.010 - 50.000
0.00000 - 500.00000
0.00000 - 10.00000
0.00000 - 10.00000
0.00000 - 500.00000
0.00000 - 10.00000
- 140 -
Contents
Unit
s
Definite time reset delay
Dependent reset time multiplier in
-
IEEE inverse curve
Dependent reset time multiplier in
-
US inverse curve
Dependent reset time multiplier in
-
Original inverse curve
-
User original curve coefficient
-
User original curve coefficient
-
User original curve coefficient
-
User original curve coefficient
-
User original curve coefficient
6F2S1931 (0.20)
Default
0.00
1.000
1.000
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)