Toshiba GR200 Series Instruction Manual page 529

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Selection of slave protocol
Ethernet modules are provided for the IEC61850 and other communication†, and an serial
module‡ will be provided optionally for the Modbus RTU or IEC60870-5-103 slave
communication.
Figure 10.1-1 illustrates the IED has IEC61850, IEC103 and Modbus, and the user can select
one of three using SLAVE PROTOCOL setting of Communication sub-menu. IEC61850 and
others have its own settings. For example, an IED has IEC61850 settings, such as [GOINT],
whereas it has IEC103 settings, such as [103ADDR].
Communication
10:48
1/7
LAN
>
USBCOM
>
RS485
>
SLAVE PROTOCOL
>
IEC61850
>
IEC103 SLV
>
MODBUS
>
†Note: Selection and operation is dependent on the IED configurations, which the
customer has determined with the ordering code. Accordingly, the selection and
operation can be unavailable if the protocol is not provided (see p.514). To examine
the IED configuration, check your ordering code referring
DNP3.0 is not supported here (even though the DNP3.0 is displayed on the LCD).
‡Note: We have discussed that optional communication interface (see
description: Signal processing and communication module
CNM_SLAVE (Function ID: 300001)
Setting item
Slave Protocol
IEC61850 / IEC103 / Modbus
Element ID
Name
3100013406
ProcType
SLAVE PROTOCOL
10:48
Slave Protocol
IEC61850
Figure 10.1-1 SLAVE PROTOCOL setting
Range
Protocol selection
- 515 -
1/1
+
Contents
Description
A type of the protocol selected in the IED
6F2S1931 (0.20)
SLAVE PROTOCOL
10:48
1/4
IEC61850
IEC103
DNP3.0†
Modbus
Appendix: Ordering
.
Technical
).
Default setting value
IEC61850
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)