a. View from connector edge
C11
C12
Fiber optic module
5.
Fiber optic module is used for the serial communication in the IEC 60870-5-103 standard.
IRIG-B000 module
6.
IRIG-B000 module is used to receive the digital signal generated with an external clock; the
signal is in conformity to serial IRIG-B000 format. Note that the IRIG-B000 module is able to
receive digital signal (TTL) only (i.e., the reception of AM signal is not applicable). This module
is isolated using a photo coupler; the user should note A2 and B2 connectors are not used. The
peak value of IRIG-B000 signal should be greater than 3.5 volts; the IRIG-B000 module has
the input resistor (about 3k ohm). Thus, the terminal resistor can be required when the IRIG-
B000 signal is delivered for several devices; the value of the terminal resistor depends on the
PCB connector
A1
B1
COM-A(+)
A2
B2
COM-B(−)
A3
B3
COMM(GND)
0V
b. Port circuit
Figure 4.3-9 RS485 connection and module
Figure 4.3-10 Fiber optic module
- 272 -
A1
B1
A2
B2
A3
B3
Frame ground (FG)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
Sheath
A cable for
an IED
Sheath
A cable for
another
IED