Toshiba GR200 Series Instruction Manual page 715

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

simulation test. This does not start the simulation.
The setting menu is shown in the manner of the screen illustrated in Figure 11.8-7,
if the user needs to configure an Input Circuit other than BI01 (BI02 to BI18 in the
screen shown in Figure 11.8-6); the user can configure each BI signal in a manner
similar to that described for BI01.
After selecting OP in Figure 11.8-6, use the following screen to start the simulation
test.
Figure 11.8-8 Execution menu of BI test
If key ENTER is pressed in Figure 11.8-8, the status will change to test status. The
following screen will be displayed after pressing the key ENTER. Figure 11.8-9
shows that the IED is in simulation test mode.
Figure 11.8-9 Running test menu
Note: The user has to continue to depress the key ENTER on the IED front panel during
the simulation test period. The simulation status will be released if key ENTER is
not pressed.
Binary output test screen: The user is able to test a binary output circuit.
Figure 11.8-10 is an example of how to select a binary output from the Test
Mode screen.
Slot#3
10:48
Press and hold ENTER
to operate
Press <- to return
To previous page
Slot#3
10:48
Press and hold ENTER
to operate
Operating..
Press <- to return
To previous page
- 701 -
6F2S1931 (0.20)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents