03.06
Restart once the safe standstill function has been selected
1. Deselect the function in each monitoring channel via the input terminals.
2. Issue drive enable signals.
3. Cancel the power-on inhibit and power-up again.
– 1/0 edge at input signal "ON/OFF1" (cancel power-on inhibit)
– 0/1 edge at input signal "ON/OFF1" (power-up drive)
4. Move/traverse the drives again.
Status with safe standstill
The status of the safe standstill (SH) function is indicated via the following parame-
ters:
Parameter overview (see Subsection 8.2.2 "Description of parameters")
S r9772
S r9872
S r9773
S r9774
Response time for the "safe standstill" function
The following values can be specified for the response times when the function is
selected/deselected via input terminals:
S Typical response time
2x safety monitoring clock cycle CU (r9780) + inputs/outputs, sampling time
(p0799)
S Maximum response time that can occur when an error develops
4x safety monitoring clock cycle CU (r9780) + inputs/outputs, sampling time
(p0799)
Examples:
Assumption:
Safety monitoring clock cycle CU (r9780) = 4 ms and inputs/outputs, sampling time
(r0799) = 4 ms
t
= 2x r9780 (4 ms) + r0799 (4 ms) = 12 ms
R_type
t
= 4x r9780 (4 ms) + r0799 (4 ms) = 20 ms
R_max
Parameter overview (see Subsection 8.2.2 "Description of parameters")
S p0799
S r9780
S r9880
© Siemens AG, 2006. All rights reserved
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) – 03.2006 Edition
"CO/BO: SI status (Control Unit)"
"CO/BO: SI status (Motor Modules)"
"CO/BO: SI status (Control Unit + Motor Modules)"
"CO/BO: SI status (safe standstill group)"
"CU inputs/outputs, sampling time"
"SI monitoring clock cycle (Control Unit)"
"SI monitoring clock cycle (Motor Module)"
Safety Functions Integrated in the Drive
4.2 Safe standstill (SH)
4-53