Basic Parameters 2 - Toshiba TOSVERT VF-S9 Instruction Manual

Compact inverter 1-phase 200v class 0.2 2.2kw 3-phase 200v class 0.2 15kw 3-phase 400v class 0.75 15kw
Hide thumbs Also See for TOSVERT VF-S9:
Table of Contents

Advertisement

6.4

Basic parameters 2

6.4.1
• Function
Parameter setting
6
Title
*Setting value of F170 depending on the end of Type-form. AN, WN : 60Hz, WP : 50Hz
Setting of switching terminals
The terminal for switching to motor 2 needs to be set, since this function is not assigned under the default
setting. Assign this function to an idle terminal.
The parameters to be switched depend on the particular identification number of the input terminal selection
function.
Input terminal function number
40:MCHG
OFF
OFF
OFF
OFF
ON
Switching motor characteristics via terminal input
: Base frequency 2
: Torque boost 2
: Motor electronic-thermal protection level 2
Use the above parameters to switch the operation of two motors with a single inverter and to select
motor V/F characteristics (two types) according to the particular needs or operation mode.
Note: The
(V/F control mode selection) parameter is enabled only for motor 1. If motor 2 is se-
lected, V/F control will be given constant torque characteristics.
Function
Base frequency 2
Torque boost 2
Motor electronic-thermal protection level 2
39:THR2
5:AD2
OFF
OFF
OFF
ON
ON
OFF
ON
ON
-
-
Adjustment range
25 ∼ 400 (Hz)
0.0 ∼ 30.0 (%)
10 ∼ 100 (%)
Parameters to be used or switched
Parameters to be used
,
,
,
,
Parameters to be switched
,
Parameters to be switched
,
,
Parameters to be switched
,
,
,
Parameters to be switched
,
,
,
F-10
E6580757
Default setting
50 or 60
According to model
(See section 11)
100
,
,
,
,
,
,
,
,