Toshiba TOSVERT VF-S9 Instruction Manual page 79

Compact inverter 1-phase 200v class 0.2 2.2kw 3-phase 200v class 0.2 15kw 3-phase 400v class 0.75 15kw
Hide thumbs Also See for TOSVERT VF-S9:
Table of Contents

Advertisement

Parameter setting
Title
Function
Electronic thermal protection
characteristics selection
Motor electronic thermal pro-
(
)
tection level 1
1) Setting the electronic thermal protection characteristics selection
motor electronic thermal protection level 1
The electronic thermal protection characteristics selection
overload trip function (
While the inverter overload trip (
can be selected using the parameter
Explanation of terms
Overload stall: When the inverter detects an overload, this function automatically lowers the output
frequency before the motor overload trip
allows the drive to run with balanced load current frequency without a trip. This is an
optimum function for equipment such as fans, pumps and blowers with variable
torque characteristics that the load current decreases as the operating speed de-
creases.
Note: Do not use the overload stall function with loads having constant torque characteristics (such as
conveyor belts in which load current is fixed with no relation to speed).
[Using standard motors (other than motors intended for use with inverters)]
When a motor is used in the lower frequency range than the rated frequency, that will decrease the cooling
effects for the motor. This speeds up the start of overload detection operations when a standard motor is
used in order to prevent overheating.
Adjustment range
Setting
value
0
1
Standard
2
motor
3
4
VF motor
5
(special
6
motor)
7
) and the overload stall function.
) will be in constant detect operation, the motor overload trip (
.
E-19
Overload
Overload
protection
stall
×
×
×
×
×
×
×
×
10 ∼ 100 (%)
is used to enable or disable the motor
is activated. The soft stall function
E6580757
Default setting
0
100
: valid, × : invalid
and
5
)