Designated frequency
Designated frequency
Designated frequency attainment signal
P24-OUT (Default setting)
RY-RC
FLA-FLC-FLB
Speed attainment set frequency: Inverted
6.1.3
Output of set frequency speed reach signal
: Speed reach setting frequency
: Speed reach detection band
• Function
When the output frequency becomes equal to the setting of the
the
parameter, an ON or OFF signal is generated.
Parameter setting of set frequency and detection band
Title
Speed reach setting frequency
Speed reach detection band
Parameter setting of output terminal selection
Title
Function
Output terminal
selection 2 (OUT)
Note: Select the
FLA-FLC-FLB terminal output.
Output frequency [Hz]
+
Designated frequency
0
Function
Adjustment range
0 ∼ 29
(See section 11)
parameter to specify RY-RC terminal output, or the
F-3
Time [s]
parameter ± the setting of
Adjustment range
0.0 ∼
(Hz)
0.0 ∼
(Hz)
Setting
6: RCH
(Designated frequency - ON signal),
7: RCH
(Designated frequency - OFF signal)
parameter to specify
E6580757
ON
OFF
ON
OFF
6
Default setting
0.0
2.5
or