Selection of wiring devices
Voltage class
Single-phase
200V class
Three-phase
200V class
Three-phase
400V class
Note 1: Produced by Schneider Toshiba electric corporation.
Note 2: Be sure to attach a surge killer to the exciting coil of the relay and the magnetic contactor.
10
Note 3: When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect the
Of the wiring devices listed in the above table, the magnetic contactors (MC) and the overload relays (Th-Ry) are
intended for use with the Mighty J series. When using the old series (ESPER Mighty series), refer to the table
below showing the correspondence between the two series.
ESPER Mighty series
Non-fuse circuit
Capacity of
applicable
Inverter model
motor
Rated
(kW)
current
0.2
VFS9S-2002PL
0.4
VFS9S-2004PL
0.75
VFS9S-2007PL
1.5
VFS9S-2015PL
2.2
VFS9S-2022PL
0.2
VFS9-2002PM
0.4
VFS9-2004PM
0.75
VFS9-2007PM
1.5
VFS9-2015PM
2.2
VFS9-2022PM
3.7
VFS9-2037PM
5.5
VFS9-2055PL
7.5
VFS9-2075PL
11
VFS9-2110PM
15
VFS9-2150PM
0.75
VFS9-4007PL
1.5
VFS9-4015PL
2.2
VFS9-4022PL
3.7
VFS9-4037PL
5.5
VFS9-4055PL
7.5
VFS9-4075PL
11
VFS9-4110PL
15
VFS9-4150PL
Selection of surge killers for Toshiba magnetic contactors
200V class: Surge absorbing units are optionally available for Toshiba C11J to C65J, or
Model SS-2 for C50J and C65J
400V class: For the operation and control circuits, regulate the voltage at 200V or less with a step-down
transformer.
contacts 2a in parallel to increase reliability.
Magnetic contactor (MC)
Mighty J series
C12A
C20A
C35A
C50A
C65A
Magnetic contactor
breaker
(MC)
(MCCB)
Type
Rated
Type
Note1)
current
Note1)
(A)
(A)
10
NJ30N
11
C11J
15
NJ30N
11
C11J
20
NJ30N
11
C11J
30
NJ30N
18
C20J
40
NJ50E
35
C35J
5
NJ30N
11
C11J
5
NJ30N
11
C11J
10
NJ30N
11
C11J
15
NJ30N
11
C11J
20
NJ30N
13
C13J
30
NJ30N
26
C25J
50
NJ50E
35
C35J
60
EJ100F
50
C50J
100
EJ100F
65
C65J
125
EJ225F
80
C80A
5
NJ30N
9
C11J
10
NJ30N
9
C11J
15
NJ30N
9
C11J
20
NJ30N
13
C13J
30
NJ30N
17
C20J
30
NJ30N
25
C25J
50
EJ50E
33
C35J
60
EJ100F
48
C50J
ESPER Mighty series
C13J
T11A
C20J
T20A
C35J
T35A
C50J
T65A
C65J
J-2
E6580757
Overload relay
Earth leakage
(THR)
breaker
(ELCB)
Adjusted current
Type
Rated
(A)
Note1)
current
(For reference)
(A)
1.3
T13J
10
2.3
T13J
15
3.6
T13J
20
6.8
T13J
30
9.3
T13J
40
1.3
T13J
5
2.3
T13J
5
3.6
T13J
10
6.8
T13J
15
9.3
T13J
20
15
T20J
30
22
T35J
50
28
T35J
60
44
T65J
100
57
T65J
125
1.6
T13J
5
3.6
T13J
10
5.0
T13J
15
6.8
T13J
20
11
T13J
30
15
T20J
30
22
T35J
50
28
T35J
60
Overload relay
Mighty J series
T13J
T20J
T35J
T65J
Type
Note1)
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV60F
NJV100F
NJV225F
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV50E
NJV100F