Setting Environmental Protection; Setting Parameters By Operating Method - Toshiba TOSVERT VF-S9 Instruction Manual

Compact inverter 1-phase 200v class 0.2 2.2kw 3-phase 200v class 0.2 15kw 3-phase 400v class 0.75 15kw
Hide thumbs Also See for TOSVERT VF-S9:
Table of Contents

Advertisement

5.3

Setting environmental protection

: Automatic environment setting
• Function
This automatically programs all parameters related to inverter environmental protection (auto-restart or
ride-through control after momentary power failure, supply voltage correction, acceleration/deceleration S-
pattern).
This parameter is especially suitable for wind force or hydraulic machinery such as fans and pumps
Note: Do not use this parameter for equipment such as transporters, since it is dangerous to operate
automatically such equipment after temporary stops.
[Parameter setting]
Title
Automatic environment setting
Values of automatically programmed parameters
Title
Auto-restart control selection
Regenerative power ride-through control
Supply voltage correction
Acceleration/deceleration 1 pattern
5.4

Setting parameters by operating method

: Automatic function setting
• Function
Automatically programs all parameters (parameters described below) related to the functions by selecting
the inverter's operating method.
The major functions can be programmed simply.
[Parameter setting]
Title
Automatic function setting
Function
0: Disabled
1: Automatic setting
Function
1: At auto-restart after
1: Enabled
1: Supply voltage
1: S-pattern 1
Function
0: Disabled
1: Coast stop
2: 3-wire operation
3: External input UP/DOWN setting
4: 4-20mA current input operation
E-5
Adjustment range
0: Disabled
momentary stop
0: Disabled
1: Supply voltage cor-
corrected, output volt-
rected, output voltage
age limited
limited
0: Linear
Adjustment range
E6580757
Default setting
0
5
Default setting
Default setting
0