Automatically programmed functions and parameter set values
(F)
(R)
(RST)
(S1)
(S2)
(S3)
5
(ST)
Disabled (
Input terminals and parameters are standards programmed at the factory.
Coast stop (
Setting for coast stopping. ST (standby signal) is assigned to the S3 terminal and the operation is controlled
by the on and off of the S3 terminal.
3-wire operation (
Can be operated by a momentary push-button. HD (operation holding) is assigned to the terminal S3. A
self-holding of operations is made in the inverter by connecting the stop switch (b-contact) to the S3 termi-
nal and connecting the running switch (a-contact) to the F terminal or the R terminal.
External input UP/DOWN setting
Allows setting of frequency with the input from an external contact. Can be applied to changes of frequen-
cies from several locations. UP (frequency up signal input from external contact) is assigned to the S1 ter-
Default setting
1: Coast stop
2: Potentiometer
2: Potentiometer
1: Operation
0: Terminal board
panel
2: F
2: F
3: R
3: R
10: RST
10: RST
6: SS1
6: SS1
7: SS2
7: SS2
8: SS3
1: ST
0: Activated by
1: Always active
turning ST on
active
0: VIA/II
0: VIA/II
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
)
)
)
(
)
2: 3-wire opera-
3: External input
tion
UP/DOWN set-
ting
1: Operation
2: Potentiometer
panel
0: Terminal board
0: Terminal board
2: F
2: F
3: R
3: R
10: RST
10: RST
6: SS1
41: UP
7: SS2
42: DOWN
49: HD
43: CLR
1: Always active
1: Always active
0: VIA/II
3: UP/DOWN
-
-
-
-
-
-
-
-
-
1
-
0.1Hz
-
1
-
0.1Hz
E-6
E6580757
4: 4-20mA current
input operation
0: Terminal board
0: Terminal board
2: F
3: R
10: RST
6: SS1
38: FCHG
1: ST
0: Activated by
turning ST on
active
0: VIA/II
20%
-
-
-
-
-
-
-

Hide quick links: