10 REMOTE MONITORING

The PCS100 AVC-20 provides remote access for monitoring purposes. Following monitoring connections are
available:
Integrated Web server. Using the integrated web server, the same information as displayed on the
GDM is available on any networked PC connected to the PCS100 AVC-20. In addition, downloading
event and service information is possible from the integrated web server.
Modbus TCP. For connection to plant wide SCADA or monitoring systems the PCS100 AVC -20 has a
list of registers that can be accessed.
Email Connectivity. An email notification service can be set up to send notifications of power quality
and system events.
Communication Type
Remote Web Pages
Monitoring system
Remote notifications
Remote Web Pages
Remote Web Pages are a set of web pages that are
similar in format to the standard GDM and accessed
through the integrated web server via the GDM
Ethernet connection. Through this interface the users
can
remotely
access
parameters. Viewing and downloading of event history
and service logs is also available. Access is via the
Ethernet port of the GDM and web pages can be viewed
any standard web browser on a device connected to the
same network.
Note: for security reasons start/stop control and
parameter menus are disabled by default. However,
they can be enabled through parameter settings on the
unit.
Modbus TCP
Modbus TCP connection is also provided via the
Ethernet port of the GDM user interface.
Read Only access is available to operating parameters
such as voltages, currents and power levels.
E-mail
PCS100 AVC-20 is configurable for sending e-mail
notifications in case of power quality event or systems
internal event as faults and warnings.
Automatic sending of the service logs vie e-mail to ABB
Service can also be enabled
Description
Webserver via HTTP, Ethernet
SW upgrade via SSH
Modbus TCP
E-mail
the
status
and
operating
Port
80
22
502
Figure 10-1: PCS100 AVC-20 remote monitoring