ABB PCS100 AVC-20 User Manual page 76

Active voltage conditioner
Table of Contents

Advertisement

76
PCS100 AVC-20 User Manual
Code
Origin
Type
84
M, I
W
85
M
F
86
M,R,I
F
87
M,R,I
F
88
M
F
89
M
AB
90
R, I
AB
91
R, I
AB
108
R
F
109
R, I
F
142
M
W
167
M
W
168
M
F
169
M
W
170
M
F
192
M
W
194
System
Info
GDM Info
Description
Negative
Negative phase rotation
Phase
detected. Correct the
Rotation
phase sequence.
Output
Output over-voltage
Voltage High
detected.
Not Passed
This fault occurs when a
Tester
module has:
- not passed the factory
test, or
- failed since leaving the
factory.
IRQ
Software task IRQ not
Frequency
occurring at correct
Error
frequency.
Serial
The system (product) serial
Number Error
number in SCM and DSPE
are different.
Utility or
Utility and load RMS
Load Voltage
voltages differ by more
Error
than the maximum
correction ratio indicating
error.
Heatsink
Rectifier or Inverter
Cold
heatsink sensor error or
ambient temperature too
cold.
Enclosure
Rectifier or Inverter
Cold
enclosure sensor error or
too cold.
RFI Lead
The RFI configuration in the
Misconfigura
power modules does not
tion
match the Master map.
Protection
Protection Message Error.
Message
Error
Output short
Module output short
circuit
circuited.
CIOB Lost
Master lost
communications with Can
IO board.
CIOB Module
CIOB has an internal error
Error
preventing it from running.
CIOB Analog
CIOB Analog input signal is
IP Overrange
overrange (5%).
CIOB PTC
CIOB external PTC
Overtemp
overtemperature.
External
External transformer
Transformer
warning input active
Byp Open
The system has tried to
Retires
open the contactor too
Exceeded
many times
Recommended Action
Check the input phases are
wired to the correct input
terminal.
None
Contact your ABB Service
Agent to have the faulty
module replaced.
Replace the module.
Replace the whole master
auxiliary module as a complete
unit.
Repair the sensors.
Replace faulty Rectifier or
Inverter.
Check ambient temperature.
Repair the sensors if broken.
Check the part numbers of the
power modules are correct for
this machine.
Check cables.
Check system for shorts.
Check connections and fix
faulty CIOB if necessary.
Remove commissioning mode
or fix faulty CIOB
Select correct mode or setup
source for the CIOB inputs
correctly
Correct the source of the
trigger in the external system
Repair the source of the
external transformer warning
Info only