ABB PCS100 AVC-20 User Manual page 44

Active voltage conditioner
Table of Contents

Advertisement

44
PCS100 AVC-20 User Manual
7 segment LED display
OFF
Module number
L0 and module number
FLASH (50% duty, 1sec period)
L1 and module number
FLASH (50% duty, 1sec period)
E0 and module number
FLASH (50% duty, 1sec period)
E1 and module number
FLASH (50% duty, 1sec period)
E2 and module number
FLASH (50% duty, 1sec period)
E3 and module number
FLASH (50% duty, 1sec period)
rE and module number
FLASH (50% duty, 1sec period)
Ou and module number
FLASH (50% duty, 1sec period)
OK LED
OFF
ON
FLASH (50% duty, 1sec period)
RUN LED
OFF
ON
FLASH
Product Status or Description
Not powered
PCS100 AVC-20 is running
Booting. This is normal during start up.
Configuring. This is normal during start up.
A fault has occurred in the module. See error message on GDM
No communication with the main DSP (digital signal processor)
controller in the auxiliary master module. Possible DSP hardware
failure.
Problem starting the module – invalid module configuration or
invalid module parameter/s.
Communications error
The module is running, and it has been configured as rectifier
(input). This is displayed for about 2 minutes after configuration
(L1) is completed.
The module is running, and it has been configured as inverter
(output).
This
configuration (L1) is completed.
Table 6-9: 7 Segment LED Displays
Product Status or Description
Not powered
No fault and microprocessor functioning
FAULT, WARNING (temperature or overload warnings) or module boot
up stage.
Table 6-10: OK LED displays
Product Status or Description
Module stopped
Module active
Module starting
Table 6-11: RUN LED displays
is
displayed
for
about
2
minutes
after

Advertisement