PCS100 AVC-20 User Manual
Code
Origin
Type
27
M, R
AB
28
R
AB
29
R, I
F
30
R
F
31
M, R, I
F
32
I
F
33
I
F
34
I
F
35
I
F
36
I
F
37
I
F
38
I
W
39
I
F
GDM Info
Description
PLL Unlocked
The phase lock loop is not
locked to the input voltage.
This usually occurs when
the supply to the Rectifier
is switched off.
Control
Model control loop
Model
parameters out of range.
Unstable
Contactor
Second contactor
Recharge
activation before recharge
Error
delay has timed out.
Bus Not
Softcharge error if the DCV
Charging
< 0.15 PU after 200 ms, bus
not charging.
FPGA Reset
Either the FPGA (Field-
Programmable Gate Array):
- has not been reset, or
- did not initialize.
Bypass Error
Errors indicated by bypass
manager.
Bypass
Bypass SCRs enabled too
Contactor
long before bypass
Forced
contactor, detected in
hardware and contactor
forced closed.
SCR On
Bypass SCRs on too long
Timeout
when contactor remains
open (in AUTO BYPASS
mode).
SCR Not Off
Bypass SCRs remain on too
Timeout
long (not turned off) after
contactor opened from
STOP to RUN transition.
Bypass Open
With bypass open the
Error
current in inverter and
bypass CT are not the
same.
Bypass Close
With bypass closed, the
Error
inverter CT still carries
current.
Out of
One of the inverter three
Regulation
phase output RMS voltages
Warning
differs from their reference
values by more than 10%.
Out of
One of the inverter three
Regulation
phase output RMS voltages
Error
differs from their reference
values by more than 25%.
Recommended Action
Check the utility supply.
If the warning is not resolved,
contact your ABB service
agent to have the utility and
load voltage sense connection
checked.
Replace the faulty module.
Contact your ABB Service
Agent to have the fault
resolved.
Contact your ABB Service
Agent to have the fault
resolved.
Press Reset.
If the fault is not resolved,
power down and restart.
Contact your ABB Service
Agent to have the fault
resolved.
Replace the faulty module.
Replace the faulty module.
Replace the faulty module.
Contact your ABB Service
Agent to have the fault
resolved.
Contact your ABB Service
Agent to have the fault
resolved.
No action required.
Check voltage sensing circuits
including master DB9 cables.
Replace Inverter module.