ABB PCS100 AVC-20 User Manual page 46

Active voltage conditioner
Table of Contents

Advertisement

46
PCS100 AVC-20 User Manual
Start the PCS100 AVC-
20
Stop the PCS100 AVC-
20
Reset the PCS100 AVC-
20
Start Inhibit
Figure 7-2: Start button
The Start button is visible when the PCS100 AVC-20
status is Bypass (Off).
Press the Start button and press "Yes" at the
confirmation screen. The PCS100 AVC-20 will
transition to RUN operation in approx... 1sec.
Figure 7-3: Stop button
The Stop button is visible when the PCS100 AVC-20
status is Run.
Press the Stop button and press "Yes" at the
confirmation screen. The PCS100 AVC-20 will
transition to Bypass (Off) in approx... 1sec.
Figure 7-4: Reset button
The Reset button is visible when the PCS100 AVC-20
status is Fault.
Press the Reset button and press "Yes" at the
confirmation screen to reset a fault.
Figure 7-5: Start Inhibit button
The Inhibit button is visible when the Inhibit switch
or the remote stop input is closed.
The PCS100 AVC-20 cannot be operated until these
inputs are closed
The Inhibit switch is inside the enclosure door.
The remote stop input is on the front of the
Auxiliary Master Module, see Section 11.2. In this
state the PCS100 AVC-20 cannot be started via the
GDM control panel.
Start
Button
Stop
Button
Reset
Button
Start
Inhibit
Button