ABB PCS100 AVC-20 User Manual page 73

Active voltage conditioner
Table of Contents

Advertisement

PCS100 AVC-20 User Manual
Code
Origin
Type
50
R, I
AB/F
51
R, I
W
52
I
W
53
M
AB
54
M
AB
55
R, I
F
56
R, I
AB
57
R, I
F
58
R, I
AB
59
R, I
F
60
R, I
AB
GDM Info
Description
HW
The long-duration
Overcurrent
transistor is over current.
This may be caused by a
short circuit in the load.
Note: The limit is set by the
hardware.
Current Limit
The inverter's (or rectifier's)
current exceeds 110% of its
rating.
Bypass
Bypass Current High.
Current High
System HW
The load's current exceeds
Overcurrent
the rating of Inverter. There
may be short term transient
over currents. Note: The
limit set by the hardware.
System
The load current is near the
Current High
limit. The limit is 160% of
Inverter rating. Note: The
limit is set by the software.
Sine Filter
The PTC (Positive
Over Temp
Temperature Coefficient
thermistor) in module sine
filter choke indicates
temperature is too high.
Heatsink Hot
The inverter's (or rectifier's)
heat sink is too hot.
Note: A sensor is mounted
on the heat sink.
Heatsink
The inverter's (or rectifier's)
Over Temp
heat sink is too hot.
Note: A sensor is mounted
on the heat sink.
Enclosure
The inverter (or rectifier's)
Hot
enclosure's internal
temperature is too hot
(near limit).
Note: The temperature is
monitored by a thermistor
in enclosure.
Enclosure
The inverter (or rectifier's)
Over Temp
enclosure's internal
temperature is too hot
(over the limit).
Note: The temperature is
monitored by a thermistor
in enclosure.
Transistor
The inverter's (or rectifier's)
Case Hot
IGBT (Insulated Gate Bipolar
Transistor) case temp is too
hot (near limit).
Note: The temperature is
calculated using a thermal
model.
Recommended Action
Investigate the load for short
circuits.
Reduce the load's current to
maintain full protection.
No action required.
Ensure that the load is
suitable.
Reduce the load's current to
maintain full protection.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
73