ABB PCS100 AVC-20 User Manual page 74

Active voltage conditioner
Table of Contents

Advertisement

74
PCS100 AVC-20 User Manual
Code
Origin
Type
61
R, I
F
62
R, I
W/AB
63
M, R, I
W/AB
64
R,I
AB
65
I
AB
66
M
W
67
M, R, I
W
68
M, R, I
F
69
M
F
70
M
F
GDM Info
Description
Transistor
The inverter's (or rectifier's)
Case
IGBT (Insulated Gate Bipolar
OverTemp
Transistor) case
temperature is too hot
(over the limit).
Note: The temperature is
calculated using a thermal
model
Transistor
The IGBT junction is too hot
Junction Hot
(near limit).
Note: The temperature is
calculated using a thermal
model.
Copper Hot
The choke winding is too
hot (near limit).
Note: The temperature is
calculated using a thermal
model.
Copper Over
The choke winding is too
Temp
hot.
Note: The temperature is
calculated using a thermal
model.
Bypass Over
Long duration bypass over
Temp
temperature detected.
Transformer
Transformer is too hot.
Hot
Note: The temperature is
detected by a thermistor in
transformer winding.
VCAN
There is sustainable
Warning
interference in the module
communications cables.
VCAN Error
There was a non-
recoverable
communications error
between the master and the
inverter.
Rectifier Lost
The Master controller lost
communications with
Rectifier module.
Inverter Lost
The Master controller lost
communication with the
Inverter module.
Recommended Action
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
None
Ensure all module fans are
operating.
Ensure the ambient
temperature is not too high.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
- Check ribbon cables between
modules
- Call service agent
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pcs100 avc-40

Table of Contents