ABB PCS100 AVC-20 User Manual page 70

Active voltage conditioner
Table of Contents

Advertisement

70
PCS100 AVC-20 User Manual
Code
Origin
Type
10
R,I
W
11
R,I
AB
12
R,I
F
13
R,I
F
14
R, I
F
15
R, I
F
18
M, R, I
W
19
M, R, I
F
20
M, R, I
W
21
R,I
F
22
R,I
F
23
R
F
24
R
F
25
R
AB
26
R
W
GDM Info
Description
DC Bus
DC Bus Voltage Low.
Voltage Low
DC Bus
DC Bus Undervoltage.
Undervoltage
Zero Seq
Inverter module zero
Current High
sequence current is too
high.
Zero Seq Abs
The PCS100 Module's
Current High
absolute zero sequence
currents are too high.
Sync Lost
The inverter and/or rectifier
Failure
lost synchronization with
master.
Sync Lock
The inverter and/or rectifier
T/O
cannot synchronize with the
master within the timeout
period.
Control Loop
Sustainable internal
Timing
condition. Control Loop
processing result late.
Internal Error
There was an internal error.
Stack Level
DSP stack has reached 75%
Warning
threshold level.
Contactor
The pre-charge or bypass
Activate T/O
contactor has not opened
within the required time-
out period.
Contactor
The pre-charge or bypass
Deactivate
contactor has not de-
T/O
activated (auxiliary contact
detection) within the
required time-out period.
Precharge
Precharge relay &
Timeout
softcharge resistor is
enabled for too long.
Softcharge
Errors indicated by the
Error
softcharge manager.
Softcharge
The softcharge sequence
Timeout
takes too long, causing
restart sequence.
DC Bus
DC Bus ripple voltage high.
Ripple High
Recommended Action
No action required.
The PCS100 AVC-20 will
automatically recover when
the input power returns to
normal.
No action required.
The PCS100 AVC-20 will
automatically recover when
the input power returns to
normal.
Contact your ABB Service
Agent to have the fault
resolved.
Contact your ABB Service
Agent to have the fault
resolved.
Check all communication
cables.
Ensure all communication
cables are connected and not
damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
Press Reset.
If the warning is not resolved,
power down and restart.
Press Reset.
If the fault is not resolved,
power down and restart.
Power down and restart.
Notify your ABB Service Agent.
Replace the faulty module.
Replace the faulty module.
Replace the faulty module.
Replace the faulty module.
Replace the faulty module.
Check all three phases are
present.