Technical Specification; Model Range; Utility - Input - ABB PCS100 AVC-20 User Manual

Active voltage conditioner
Table of Contents

Advertisement

PCS100 AVC-20 User Manual

4 TECHNICAL SPECIFICATION

NOTE: These specifications apply to the standard PCS100 AVC-20 range and may be superseded by special
variations stated on the PCS100 AVC-20 rating label or User Manual Addendum.

4.1 Model Range

Power range
4.2 Utility – Input
Rated voltage (model specific)
Maximum supply voltage
Nominal supply frequency
Frequency tolerance
Power system
Overvoltage category
Fault capacity
Outage – control ride through
Harmonics
250 – 3000 kVA
400 V – application range 380 V - 415 V
Note: Application voltage lower than the rated voltage results in
power derating. Consult the rating tables for more information.
130%
50 Hz or 60 Hz
± 5 Hz
3-phase + Neutral (4-Wire)
Centre ground referenced (TN-S)
III
Refer to the model tables shown in this document.
> 600 ms
IEC 61000-2-4 Class 2 (THD
< 8%)
V
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pcs100 avc-40

Table of Contents