ABB PCS100 AVC-20 User Manual page 72

Active voltage conditioner
Table of Contents

Advertisement

72
PCS100 AVC-20 User Manual
Code
Origin
Type
40
I
F
41
I
F
42
M
F
43
M
F
44
M
F
45
M
F
46
M
W
47
M
F
48
R
AB
49
R, I
W
GDM Info
Description
SDI Cmd
The Streaming Data
Error
Interface error count is too
high.
SDI Mode
Non-recoverable internal
Error
fault.
Initialisation
A setting is out of range.
Failure
Fault Reset
The master was not able to
Timeout
reset a fault in an inverter
or rectifier module.
Parameter
The master could not
Error
access a setting from
Downstream
within the inverter or
rectifier.
Unexpected
Bypass activated for
Bypass
unknown reason. Bypass
activation not reported to
the master.
Inverter
There is a variation in
Unbalanced
current level between
inverter modules above
threshold.
DC Bus
Difference in DC Bus
Unequal
voltages between rectifier
and inverter is above
threshold.
DC Bus
DC Bus undervoltage –
Uncontrolled
lower than U
*correction – the control
loop does not have enough
headroom to control
inductor voltages.
HW Current
The short duration
High
transistor current is too
high.
Note: The limit set by the
hardware.
Recommended Action
Contact your ABB Service
Agent to have the fault
resolved.
Contact your ABB Service
Agent to have the fault
resolved.
Contact your ABB Service
Agent to have the fault
resolved.
Ensure all communication
cables are connected and not
damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
If there is no damage and the
fault is not resolved, power
down and restart.
Ensure all communication
cables are connected and not
damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
If there is no damage and the
fault is not resolved, power
down and restart.
Contact your ABB Service
Agent to have the fault
resolved.
Check all inverters are
operating.
Contact your ABB Service
Agent to have the fault
resolved.
Check the incoming AC voltage
*sqrt (2)
is not too high.
RMS
Reduce the load's current to
maintain full protection.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pcs100 avc-40

Table of Contents