Mitsubishi Electric GOT1000 Series Connection Manual page 288

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

8.2.3
Connecting to PC2J, PC2JS or PC2JR
For the RS-422 connection
PC2J
Link unit
PC2JS
PC2JR
Connection cable 1)
PLC
Model
Communication
*1
Link unit
name
Type
PC2J
PC/CMP2-
PC2JS
LINK
RS-422
PC2JR
(THU-5139)
*1
The link unit is a product manufactured by JTEKT Corporation.For details of the product, contact JTEKT Corporation.
*2
Connect it to the RS-232 interface (built into GOT). It cannot be mounted on GT1655 and GT155 .
8 - 6
8. CONNECTION TO JTEKT PLC
8.2 System Configuration
PC2J
Link unit
PC2JS
PC2JR
Connection cable 1)
Connection cable 2)
Cable model
Connection diagram
Connection diagram number
number
RS422 connection
GT09-C30R41201-6C(3m)
GT09-C100R41201-6C(10m)
RS422
GT09-C200R41201-6C(20m)
connection diagram 5)
GT09-C300R41201-6C(30m)
RS422 connection
GOT
Connection cable 2)
Max.
Cable model
distance
500m
diagram 1)
500m
or
diagram 8)
Communication driver
JTEKT TOYOPUC-PC
GOT
Number of
connectable
Option device
Model
equipment
- (Built into GOT)
GT16-C02R4-9S
(0.2m)
*2
GT15-RS2T4-9P
32 PLCs for
1 GOT
GT15-RS4-9S
- (Built into GOT)

Advertisement

Table of Contents
loading

Table of Contents