3.7 Precautions

Station number setting of the temperature controller system
• When connecting to DMC10 or SDC
Make sure to establish temperature controller system with No.1 station.
• When connecting to DMC50/AHC2001
A COM module or temperature controller with the station number set with the host address must be included.
GOT clock control
Since the control equipment does not have a clock function, the settings of "time adjusting" or "time broad cast" by
GOT clock control will be disabled.
Disconnecting some of multiple connected equipment
The GOT can disconnect some of multiple connected equipment by setting GOT internal device. For example, the
faulty station where a communication timeout error occurs can be disconnected from connected equipment.
For details of GOT internal device setting, refer to the following manual.
When DMC50/AHC2001 and DMC10/SDC are mixed
GOT does not support connections with DMC50 and DMC10/SDC mixed.
Station number range of AHC2001
Although the station number range of AHC2001 is 1 to 127, use the station number range of DMC50 of 1 to 15.
Device range of AHC2001
The GOT does not support all the devices of AHC2001.
Use AHC2001 with the GOT within the device range equivalent to that of DMC50.