Got Side Settings - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

5.4 GOT Side Settings

5.4.1
Setting communication
interface (Communication
settings)
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: OMRON
• Controller Type: OMRON THERMAC/INPANEL
NEO
• I/F: Interface to be used
• Driver: OMRON THERMAC/INPANEL NEO
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
5.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
5 - 12
5. CONNECTION TO OMRON TEMPERATURE CONTROLLER
5.4 GOT Side Settings
Click!
[Controller Setting] from the
5.4.2
Make the settings according to the usage environment.
3.
4.
Item
Transmission Speed
Data Bit
Stop Bit
Parity
Retry
Timeout Time
Delay Time
Format
Communication detail settings
Description
Set this item when change the
transmission speed used for
communication with the
connected equipment.
(Default: 9600bps)
Set this item when change the
data length used for
communication with the
connected equipment.
(Default: 7bits)
Specify the stop bit length for
communications.
(Default: 2bits)
Specify whether or not to
perform a parity check, and
how it is performed during
communication.
(Default: Even)
Set the number of retries to be
performed when a
communication error occurs.
(Default: 0time)
Set the time period for a
communication to time out.
(Default: 3sec)
Set this item to adjust the
transmission timing of the
communication request from
the GOT.
(Default: 2ms)
Select the communication
format.
(Default: 1)
format 1: only continuous
access
format 2: continuous and
random access
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
3 to 30sec
0 to 300 (ms)
1/2

Advertisement