Mitsubishi Electric GOT1000 Series Connection Manual page 211

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

4.3.3
PLC side setting
POINT
POINT
POINT
OMRON PLC
For the communication between OMRON PLC and GOT, use the FINS communication.
For the FINS communication, the node must be specified according to the realm of FINS. However, for the
Ethernet network, the data transfer according to the IP address is required.
• Automatic conversion method (dynamic)
• Automatic conversion method (static)
• IP address table conversion method
• Combined method
The following four methods are available for converting the FINS node address to the IP address.
For details of OMRON PLCs, refer to the following manual.
OMRON PLC user's Manual
Communication settings
For the PLC communication setting, set with a software for programming apparatus (CX-Programmer Ver.3.20 or
later).
(1) CX-Programmer setting
Item
Automatic conversion method
Global
*1
IP address
Subnet Mask
[255]. [255]. [255]. [0]
*1
FINS UDP port
Ethernet
module
IP address
Automatic conversion
conversion
CPU
highly-
IP address table
functional
Transmission
module
Automatic detection (Default)
speed
Node IP Address
dynamically
*2
change
*1
Set the same [IP address] and [FINS UDP Port] settings as that of [IP address] and [Port No.] of the GT Designer3 Ethernet
setting.
*2
The Node IP Address dynamically change function is available only when the Ethernet module to be used is Ver.1.3 or later.
For the setting, set in the module setting of CX-ProgrammerVer.5.0 or later or in the WEB function.
For details of Node IP Address dynamically change, refer to the following manual.
*3
Set the same lowermost bit of the [IP address] setting as that of the node setting switch of the module.
*4
Set the same [GOT Port No. (Communication)] In Communication detail settings as that of [Port No.] of the Ethernet setting.
*5
Set the same lowermost bit of the [GOT IP address] in Communication detail settings as that of [GOT PLC No.].
*6
Set the same lowermost bit of the [GOT IP address] and [GOT PLC No.] in Communication detail settings of GT Designer3 as
that of [IP address table].
Automatic conversion
*4
(dynamic)
method (static)
All 1 (Default)
All 1 (Default)
*3
[192]. [168]. [0]. [1]
[192]. [168]. [0]. [1]
[255]. [255]. [255]. [0]
9600
Automatic conversion
method (dynamic)
method (static)
-
Automatic detection (Default)
Change dynamically
Change dynamically
(Default)
OMRON PLC user's Manual
Setting range
IP address table method
*4*5
All 1 (Default)
*3
[192]. [168]. [0]. [1]
[255]. [255]. [255]. [0]
9600
9600
IP address table method
10 [192]. [168]. [0]. [1]
-
11 [192]. [168]. [0]. [18]
Automatic detection (Default)
Change dynamically
(Default)
(Default)
4. CONNECTION TO OMRON PLC
4.3 Ethernet Connection
*4*6
*4*6
Combined method
All 1 (Default)
[192]. [168]. [0]. [1]
[255]. [255]. [255]. [0]
9600
Combined method
10 [192]. [168]. [0]. [1]
Automatic detection (Default)
Change dynamically
(Default)
4 - 39
1
2
3
4
5
6
7
8

Advertisement

Table of Contents
loading

Table of Contents