Set the device address for the ABB OTM ATS. The addresses of devices connected to a same
port must be unique. When creating an ABB OTM ATS on the ECC500 WebUI, enter this
value in Equipment Address.
Step 7 Press ESC to return to the home screen.
----End

4.4.11 Setting the PD510 Coulometer Device Address

Prerequisites
Procedure
Step 1 Hold down PROG/ESC for 3s on the display panel of the PD510 coulometer and enter the
correct password.
Step 2 Press ENTER.
Step 3 SyS is displayed. Then press ENTER.
Step 4 Set communications parameters.
Table 4-10 Parameter description
Parameter
Addr
bAUd
Pro
DataBit, StopBit, and Parity for the PD510 coulometer cannot be set on the WebUI. Their
values are 8, 1, and None respectively.
Step 5 After the modification, hold down PROG/ESC for 3s to return to the home page so that the
configuration is completed.
----End
Issue 05 (2020-03-16)
The device address planned for the PD510 coulometer is obtained.
The PD510 coulometer is powered on.
The preset password is 1000. To protect the access security, change the password after logging in to the
coulometer for the first time.
Copyright © Huawei Technologies Co., Ltd.
Description
Indicates the device address planned for the PD510
coulometer. The devices with the same address cannot
connect to the same port. When creating a PD510 coulometer
on the ECC500 WebUI, enter this value in Equipment
Address.
Indicates the baud rate. The default baud rate is 9600.
rtu
4 Installation and Commissioning
51