Mue05A_Aidi_1 Di Alarm - Huawei ECC500 User Manual

Hide thumbs Also See for ECC500:
Table of Contents

Advertisement

ECC500
User Manual
Attribute
Alarm ID
22634
Impact on the System
After this alarm is generated, the WebUI stops updating parameter values of undetected
equipment and fails to send configuration signals. Maintain the equipment immediately.
Possible Causes
Procedure
Step 1 Securely insert the board and tighten the screws.
Step 2 Replace the faulty board.
----End
Clearing
This alarm is cleared when the board is securely inserted into the subrack and the
communication between the board and the ECC500 resumes.

6.2.2.2 MUE05A_AIDI_1 DI Alarm

Description
This alarm is generated when the normally open (NO) dry contacts are closed or the normally
closed (NC) dry contacts are open.
Attribute
Alarm ID
22635
Impact on the System
After this alarm is generated, equipment keeps running properly, but the sensors need to be
maintained immediately.
Issue 05 (2020-03-16)
The board is not securely inserted.
The board is removed.
The board is faulty.
Copyright © Huawei Technologies Co., Ltd.
Alarm Severity
Set to Major by default.
Alarm Severity
Set to Minor by default.
6 Maintenance and Troubleshooting
Alarm Type
Equipment alarm
Alarm Type
Equipment alarm