5.2.3 Adding Dry Contact Devices

5.2.3.1 Adding a Smoke Sensor

Prerequisites
Context
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > MUE05A Expansion Card > MUE05A4 > Running Parameter >
AI/DI_1 Port Settings.
Step 3 Set AI/DI_1 Sensor to Enable.
Step 4 Click Submit.
Step 5 Set AI/DI_1 Sensor Name, for example, to Smoke_sensor.
Step 6 Check whether Smoke Sensor is automatically displayed in AI/DI_1 Sensor Type.
Step 7 Set AI/DI_1 Power Supply to On.
Step 8 Click Submit.
Figure 5-9 Adding a smoke sensor
----End
Issue 05 (2020-03-16)
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
A smoke sensor should be connected to the AI/DI_1 port on the MUE05A4 of the
ECC500 by default. To connect the smoke sensor to another port, set the port parameters
using the following method.
A smoke sensor can be automatically identified. After it is connected to an AI/DI port on
the ECC500. The sensor type is automatically identified and displayed in AI/DI_1
Sensor Type on the ECC500 WebUI.
Figure 5-9
shows the configured page.