Toggles 1 to 6 of the DIP switch specify the device address in binary mode. ON indicates 1,
and OFF indicates 0.
Table 4-3 Mapping between T/H sensor device addresses and DIP switch settings
Device
Toggle
Address
Switch 1
1
ON
2
OFF
3
ON
4
OFF
----End

4.4.2 Setting the WS332M2-5 T/H Sensor Device Address

Procedure
Step 1 Hold down SET on the display panel of the T/H sensor for 2 seconds.
Step 2 When Add is displayed, set the device address by pressing + and -.
----End

4.4.3 Setting the UPS2000-G-A Device Address

Context
UPS2000-G-A V100R001 is used and equipped with an LCD screen, as shown in
4-25.
Figure 4-25 LCD screen display
Procedure
Step 1 Operate the DIP switch S2 on the optional Modbus card to set the UPS2000-G-A device
address.
Issue 05 (2020-03-16)
Table 4-3
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
Copyright © Huawei Technologies Co., Ltd.
shows an example of the switch settings.
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
4 Installation and Commissioning
Toggle
Toggle
Switch 6
Switch 7
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Toggle
Switch 8
OFF
OFF
OFF
OFF
Figure
45