5.2.9 Adding a PD510 Coulometer

Prerequisites
Context
After a PD510 coulometer is connected to the ECC500, add the PD510 coulometer on the
ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select PD510 from the Equipment Type drop-down list box and set device parameters, as
shown in
Figure 5-24 Adding a PD510 coulometer
Table 5-11 PD510 coulometer parameters
Parameter
Communication
Board Slot
Issue 05 (2020-03-16)
A PD510 coulometer is connected to the ECC500. The PD510 coulometer and ECC500
have been powered on.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Figure
5-24.
Table 5-11
Setting
Select 3 from the drop-down list box.
NOTE
Copyright © Huawei Technologies Co., Ltd.
describes the setting methods.
The setting example indicates that the PD510 coulometer is connected to
the COM2 port of the RS485 card in slot 3 of the ECC500. If the PD510
coulometer is connected to another port, set the slot number for the
connected port.
5 UI Description
78