Procedure
Step 1 Prepare an RJ45 connector on one end of a network cable, as shown in
Figure 4-13 Preparing an RJ45 connector (unit: mm)
Step 2 Prepare an RJ12 connector on the other end of the cable, as shown in
Figure 4-14 Preparing an RJ12 connector (unit: mm)
Step 3 Plug the RJ45 connector to an RS485 port with 12 V power supply in the ECC500 and the
RJ12 connector to the RS485 port in the T/H sensor.
----End

4.3.5.3 Connecting the WS332M2-5 T/H Sensor Monitoring Cable

Context
The cable connection method described in the section applies to cable connections from the
ports of the RS485 expansion card in the ECC500 to devices.
Issue 05 (2020-03-16)
The cable connection method described in the section applies to cable connections from
the ports of the RS485 expansion card in the ECC500 to devices.
Copyright © Huawei Technologies Co., Ltd.
4 Installation and Commissioning
Figure
4-13.
Figure
4-14.
35