Setting The Abb Otm Ats Device Address - Huawei ECC500 User Manual

Hide thumbs Also See for ECC500:
Table of Contents

Advertisement

ECC500
User Manual
Step 3 Tap Communication.
Set Serial port baud rate and Serial port address.
Table 4-9 Parameter description
Parameter
Serial port baud rate
Serial port address
The DataBit, StopBit, and Parity for the PDU8000 cannot be set on the WebUI. Their default
values are 8, 1, and None respectively.
----End

4.4.10 Setting the ABB OTM ATS Device Address

Prerequisites
Procedure
Step 1 On the display panel of the ABB OTM ATS, press
Step 2 Press
Step 3 Press
Step 4 Enter the password and press
Step 5 Press
Step 6 Press
Issue 05 (2020-03-16)
The preset user name and password for the PDU8000 are respectively admin and 000001. To ensure
access security, change the password upon first use.
You have obtained the device address assigned to the ABB OTM ATS.
The ABB OTM ATS has been powered on.
to move the cursor to Device Configuration.
.
The preset password is 0001. To ensure access security, change the password upon first use.
to move the cursor to Modbus.
. On the Modbus parameter setting screen, set communications parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Retain the default value 9600.
Indicates the device address assigned to the
PDU8000. The addresses of devices
connected to a same port must be unique.
When creating a PDU8000 on the ECC500
WebUI, enter this value in Equipment
Address.
.
.
4 Installation and Commissioning
50