FusionModule1000A20 IT Solution
Installation Guide (2016.05, AI Version)
2.
3.
Step 6 (Optional) Install the electric control head.
Do not install the electric control head when installing the fire cylinder for the first time.
Install the electric control head when commissioning the fire extinguishing system.
1.
If the ejector is not reset, extinguishant may be released due to misoperations.
Issue 02 (2017-01-10)
Figure 9-10 Connecting the fire cylinder to the fire extinguishing pipeline
Connect the I-shaped connection pipe to the threaded adapter.
Connect one end of the high-pressure hose to the fire cylinder and the other end to the
fire extinguishing pipeline, as shown by (2) in
Verify that the electric control head ejector is reset. If the ejector is not reset, press the
ejector.