System data for PM240-2 Blocksize Power Modules

Table 3- 1
Electrical data for the blocksize format
Line connection voltage
Devices FSA to FSC
Devices FSD to FSF
Device FSG
Line supply types
Power Modules without integrated filter
Power Modules with integrated filter
Line frequency
Line power factor for line supply voltage 3 AC and type
rating
Devices FSA to FSC
Devices FSD to FSG
Electromagnetic compatibility
Noise immunity
noise emission
For devices with integrated radio interference
suppression filter
Standard
FSF/FSG devices with 690 V line supply voltage
For devices without integrated radio interference
suppression filter with optional external radio
interference filter for grounded line supplies
For devices without integrated radio interference
suppression filter for operation on IT line supplies
Overvoltage category
Electronics power supply
Rated short-circuit current (SCCR) according to
UL 61800-5-1
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
1 AC: 200 ... 240 V ±10 % (for Power Modules up to 4 kW)
3 AC: 200 ... 240 V ±10 %
3 AC: 380 ... 480 V ±10 %
3 AC: 200 ... 240 V ±10 % (in operation -20 % < 1 min)
3 AC: 380 ... 480 V ±10 % (in operation -20 % < 1 min)
3 AC: 500 ... 690 V ±10 % (in operation -20 % < 1 min)
3 AC: 380 ... 480 V ±10 % (in operation -20 % < 1 min)
3 AC: 500 ... 690 V ±10 % (in operation -20 % < 1 min)
All line supply types TN/TT/IT
TN/TT line supplies with grounded neutral point
47 ... 63 Hz
Active factor (cos φ1): > 0.96
power factor (λ): 0.70 ... 0.85
Active factor (cos φ1): 0.98 ... 0.99
power factor (λ): 0.90 ... 0.92
All PM240-2 Power Modules are suitable for use in the second
environment.
According to EN 61800-3
Category C2
Category C3
Category C2
Category C4
III acc. to EN 61800-5-1
Safety extra-low voltage (PELV) acc. to IEC 61800-5-1
Comment:
Grounding the 24 V electronics power supply
In SINAMICS S120 components, the electronics ground M is
permanently connected to the protective conductor potential.
100 kA in conjunction with Class J fuses
SCCR in conjunction with other protective devices "Protective
devices of for PM240-2 Power Modules
(https://support.industry.siemens.com/cs/de/de/view/109486009
)".
System overview
3.5 System data
1)