Motor-side power components
7.2 Chassis
NOTICE
Risk of damaging sine-wave filter by exceeding the maximum output frequency
The maximum permissible output frequency when sine-wave filters are used is 150 Hz. The
sine-wave filter can be damaged if the output frequency is exceeded.
• When commissioning, you must always activate the sine-wave filter connected to the
NOTICE
Damage to the sine-wave filter if a motor is not connected
Sine-wave filters, which are operated without a motor being connected, can be damaged or
destroyed.
• Never operate a sine-wave filter connected to the Power Module without a connected
Note
Keep the connecting cables to the Power Module as short as possible (max. 5 m).
7.2.2.3

Dimension drawing

Mounting hole
Figure 7-8
Dimension drawing, sine-wave filter
204
Power Module (see SINAMICS S120/S150 List Manual).
motor.
Manual, 06/2019, 6SL3097-5AL00-0BP1