Table 5- 40
Technical data of the PM240-2, FSE (690 V)
Line voltage 3 AC 500 ... 690 V ±10 %
Article No.
without integrated line filter
with integrated line filter
Output current
Rated current I
1)
n
Base load current I
H
for S6 duty (40 %) l
S6
Peak current l
max
Type rating
2)
based on I
/ based on I
n
H
Rated pulse frequency
Max. pulse frequency
Power loss
without filter / with filter
Cooling air requirement
Sound pressure level LpA (1 m)
24 V DC supply
for the Control Unit
Rated input current
Resistance value of the external braking
resistor
Max. cable length
to braking resistor
Line connection L1, L2, L3,
Motor connection U2, V2, W2,
DC link connection DCP, DCN
Connection for braking resistor R1, R2,
Max. motor cable length
no EMC Category:
shielded / unshielded
with filter and shielded: EMC Category C2
Weight
without / with line filter
Rated current I
covers the load cycle for Low Overload.
1)
n
Rated power of a typical standard induction motor at 3 AC 690 V
2)
The values depend on the ambient temperature and the utilization level.
3)
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
A
A
A
A
kW
kHz
kHz
kW
l/s
dB
3)
A
A
Ω
m
m
m
kg
5.2 Blocksize Power Modules (PM240-2)
6SL3210-
1PH25-2UL0
1PH25-2AL0
52
42
62
84
45 / 37
2
4
1.07 / 1.08
83
44 ... 62
1.0
50
21
15
Screw-type terminal
Torx M8
Conductor cross section. 25 ... 70 mm
Tightening torque: 8.0 ... 10 Nm (88.5 lbf in)
Screw-type terminal
Torx M5
Conductor cross section: 10 ... 35 mm
AWG 8 ... 2)
Tightening torque: 2.5 ... 4.5 Nm (22 lbf in / 40 lbf in)
200 / 300
100
26 / 28
Power Modules
Internal
6SL3210-
1PH26-2UL0
1PH26-2AL0
62
52
74
104
55 / 45
2
4
1.30 / 1.31
83
44 ... 62
1.0
59
21
15
(AWG 6 ... 3/0)
2
(AWG 20 ... 10 /
2
26 / 28
133