Replacing A Multi-Functional Sensor - Huawei FusionModule2000 V500R002C03 Maintenance Manual

Smart modular data center
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Cente
Maintenance Guide

6.4.7 Replacing a Multi-Functional Sensor

Impact on the System
The temperature, humidity, and smoke cannot be sensed.
Preparations
Procedure
Step 1 The multi-functional sensor is clamped into a base through a slot and a buckle. Hold down the
multi-functional sensor and slide it to the side to remove the sensor.
Figure 6-40 Removing a multi-functional sensor
Step 2 Disconnect cables from the rear of the multi-functional sensor.
Step 3 Connect the cables to the reserved multi-functional sensor.
Step 4 Align the slot in the rear of the reserved multi-functional sensor with the buckle on the base,
and slide and clamp the multi-functional sensor.
Step 5 Synchronize the parameters of the multi-functional sensor on the ECC800 WebUI.
Step 6 On the WebUI of the ECC800, choose Monitoring > System > ECC800 > Controls >
Delete device with communication failure, and click Submit.
Step 7 Log in to the ECC800 WebUI, and edit the plan view by adding new devices.
Step 8 Check the parameters and communication status of the multi-functional sensor to ensure
normal communication.
----End
Issue 03 (2019-12-04)
Tools: ESD wrist strap, ESD gloves, Phillips screwdriver, step ladder, labels, marker
Material: multi-functional sensor
A reserved multi-functional sensor has a base. You can replace the old base if it is damaged or does not
match the buckle of the reserved multi-functional sensor.