Huawei FusionModule2000 V500R002C03 Maintenance Manual page 33

Smart modular data center
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Cente
Maintenance Guide
Item
Operation
Check the
Check the
availability of the
communication status
RF_Z antenna.
of the AC actuator.
Check the
After a simulated alarm
availability of the
is generated, an alarm
3G antenna.
message will be sent to
the mobile phone
number bound on the
WebUI.
Check the
Hold the temperature
availability of the
sensor probe in your
temperature
palm, and check the
sensor.
temperature displayed
for the corresponding
rack environment unit
on the WebUI.
Check the
Drip water on the water
availability of the
detection cable using a
water sensor.
cup, and view active
alarms on the WebUI.
Check the pad
Log in to the ECC800
availability.
app page through a pad,
and check the basic
information.
Issue 03 (2019-12-04)
Standard
The communication
status of the AC actuator
is normal.
The bound mobile phone
number receives the
alarm message.
Temperature displayed
for the corresponding
rack environment unit
goes up on the WebUI.
A water alarm is
generated on the WebUI.
The login is successful,
and you can browse the
basic information
(including views, alarms,
and asset information) of
the smart module.
Copyright © Huawei Technologies Co., Ltd.
4 Routine Maintenance
Troubleshooting
Off: The switch is not running.
Steady green: The switch is not
running properly or is starting.
Steady orange: The indicator
takes a self-test during startup.
Steady red: The switch does not
run properly after being
registered or alarms indicating
that the power supply, fan, or
temperature is abnormal are
generated.
If the communication status is not
normal, check whether the antenna
is shielded. If so, install the antenna
to a different position. If not,
replace the antenna.
If the bound mobile phone number
fails to receive the alarm message,
check whether the antenna is
shielded. If so, install the antenna to
a different position. If not, replace
the antenna.
If the temperature does not go up,
check whether the temperature
sensor cable is loose or
disconnected. If so, reconnect the
cable. If not, replace the
temperature sensor.
If no water alarm is displayed on
the WebUI, check whether the
water sensor cable is loose or
disconnected. If the cable is
properly connected, replace the
water sensor.
If the login is failed, check the
WiFi connection first. If the WiFi
connection is normal, check the
user name and password on the
WebUI. If you cannot browse the
basic information of the smart
module after successful login,
download the pad upgrade package,
and update the app version. If the
fault persists, replace the pad.
27